GENERAL
This GS describes the hardware specifications of the analog I/O modules that can be mounted on the safety node
unit (SNB10D) and the safety control unit (SSC10? or SSC50?).
STANDARD SPECIFICATIONS
Current Input Module
This module inputs 4 to 20 mA signals from the field.
The SAI143 can be made dual redundant.
*1: No Zener barriers can be connected to this module. An isolation barrier should be used when an intrinsic safety instrument-
ed system is used.
*2: 500 V AC when dedicated signal cable is used.
Voltage Input Module
This module inputs 1 to 5 V/1 to 10 V signals from the field.
The SAV144 can be made dual redundant.
*1: 500 V AC when dedicated signal cable is used.
Current Output Module
This module outputs 4 to 20 mA signals to the field.
The SAI533 can be made dual redundant.
GENERAL
This GS provides the hardware specifications of the digital I/O modules that can be installed in the Safety Node Unit
(SNB10D) and Safety Control Units (SSC10? and SSC50?).
STANDARD SPECIFICATIONS
Input Module
Input modules accept a contact signal from the field. SDV144 can be made dual-redundant.
If SDV144 field wiring diagnostic functions are used, the following diagnostic elements should be installed for individu-
al channels in the vicinity of the field equipment:
? SCB100 (for defective open circuit detection while accepting off signals) (*1)
? SCB110 (for defective short-circuit detection while accepting on signals) (*2)
*1: Input signals are normally off while in normal operation.
*2: Input signals are normally on while in normal operation.